An optical patch cord is a short fibre cord with a connector at each end. It links two points on a distribution frame, or connects a piece of equipment to a patch panel. It is the last link in an optical circuit, and the most handled.
The video, word for word
The trade term: patch cord. An optical patching cord. A few metres, two connectors. Even when new, it is inspected before every connection. A speck of dust on the ferrule is enough to degrade the link. Inspect, clean, connect. In that order.
Before every connection
- Step 1Inspect
The ferrule goes under the inspection probe, even on a patch cord straight out of its bag. The connector it mates with is checked too.
- Step 2Clean
If the image shows dust or an oily film: dry cleaning with a cleaning pen or cassette, then inspect again.
- Step 3Connect
Dust cap removed at the last moment, connector pushed in straight until it clicks, bend radius respected, label at each end.
What distinguishes one patch cord from another
- Fibre type
Single-mode (OS2, yellow jacket) or multimode (OM3 and OM4, aqua or violet jacket).
- Connectors
LC and SC most often, MPO or MTP for multi-fibre links.
- Polish
UPC (blue connector) or APC (green connector, angled ferrule). An APC is never mated with a UPC.
- Simplex or duplex
A single fibre, or two: one for transmit, one for receive.
- Length
Specified as exactly as possible. Too long, it clutters the rack; too short, it breaches the bend radius.
Patch cord or patch lead?
Both terms describe the same object: a short cord, terminated at both ends, used for patching. “Patch cord” is the usual term on optical distribution frames and in the operator world; “patch lead” is more common in IT racks. The job is the same.
Why a speck of dust is enough
The core of a single-mode fibre is about 9 microns across: almost ten times finer than a human hair. A speck of dust on it attenuates the signal, reflects light back towards the transmitter and can mark the opposing ferrule on contact. The link may still come up, then degrade: these are the faults that take longest to find.
In the data centre
Meet-me room, distribution frames, patching between racks: installing patch cords is part of our daily work in data centres, computer rooms and server rooms. Every intervention, however short, is followed by a documented report, with photos of your rack, in line with the site’s photo policy.
Content written by the Full Connection field team and approved by Karim Bouacida, head of the company.
Frequently asked questions
Do you really need to inspect a new patch cord?
Yes. The dust cap protects against impact, not against dust: a patch cord can come out of its bag with a dirty ferrule. Inspection takes a few seconds.
What is the difference between a patch cord and a pigtail?
A patch cord has a connector at each end. A pigtail has only one: the other end is bare, to be spliced to a fibre in the cable.
Can an APC patch cord be mated with a UPC connector?
No. The two polishes are not compatible: the contact is poor, losses are high and the ferrules can be damaged. Colour helps: green for APC, blue for UPC.
What is patch cord installation?
It means installing patch cords on an optical distribution frame or between racks, to create or change a link. In a data centre, it is most often done in the meet-me room.
Patch cords to install in a data centre?
Describe the site, the maintenance window and the objective.